Typical wiring for apartments
1. with no more than 16 monitors
...
Distance Limit
Cable Type | A | B | ∑(A+B) Sum of Length |
---|---|---|---|
2 x 0.75 mm² | 60 M | 90 M | 200 M |
2 x 1.00 mm² | 75 M | 100 M | 220 M |
UTP cable (4 + 4 Combine) | 40 M | 40 M140 M |
2. with no more than 32 monitors
Distance Limit
Cable Type | A | B | ∑(A+B) | C | ∑C |
---|---|---|---|---|---|
2 x 0.75 mm² | 60 M | 90 M200 M | 90 M200 M | ||
2 x 1.00 mm² | 75 M | 100 M220 M | 100 M | 220 M | |
UTP cable | 40 M | 40 M | 140 M | 40 M | 40 M |
3. with no more than 48 monitors
...
Distance Limit
Cable Type | AB | ∑(A+B) | C∑C | D | ∑D | Cat5 | ||
---|---|---|---|---|---|---|---|---|
2 x 0.75 mm² | 60 M | 90 M | 200 M | 90 M200 M | 90 M200 M | 80 M | ||
2 x 1.00 mm² | 75 M | 100 M | 220 M | 100 M | 220 M | 100 M | 220 M | 80 M |
UTP cable | 40 M | 40 M | 140 M | 40 M | 40 M | 40 M | 40 M | 80 M |
4. with no more than 64 monitors
Distance Limit
Cable Type | A | B | ∑(A+B) | C/D/E∑C/D/E | Cat5 |
---|---|---|---|---|---|
2 x 0.75 mm² | 60 M | 90 M | 200 M | 90 M200 M | 80 M |
2 x 1.00 mm² | 75 M | 100 M | 220 M | 100 M220 M | 80 M |
UTP cable 40 M | 40 M140 M | 40 M | 40 M | 80 M |