IX-LIFT: Lift control
Lift control requires at least 2 modules
IX-RLC as main module
2. IX-LIFT as relay actuator
IX-LIFT Connectors and Indicators:
Address setting: DIP switch for address settings.
Relay outputs RL1~RL14: 14 relays NC or NO output for lift control.
Relay LED(Under): relay output RL1~RL14 LED indicator. Lights on when trigger.
Card Read, IX-Lift connector: use for lift controller.
Power LED: Power led, lights while power on
RS485: Inner communication ports connect with IX-RLC or IX-LIFT
Wiring IX-RLC with IX-LIFT
Control Signal Outputs
IX-LIFT DIP switch and floors
IX-LIFT DIP switch:
Relays and floors:
Relay | RL1 | RL2 | RL3 | RL4 | RL5 | RL6 | RL7 | RL8 | RL9 | RL10 | RL11 | RL12 | RL13 | RL14 |
Floor | 00 | 01 | 02 | 03 | 04 | 05 | 06 | 07 | 08 | 09 | 10 | 11 | 12 | 13 |
IX-LIFT DIP switch:
Relays and floors:
Relay | RL1 | RL2 | RL3 | RL4 | RL5 | RL6 | RL7 | RL8 | RL9 | RL10 | RL11 | RL12 | RL13 | RL14 |
Floor | 14 | 15 | 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 | 25 | 26 | 27 |
IX-LIFT DIP switch:
Relays and floors:
Relay | RL1 | RL2 | RL3 | RL4 | RL5 | RL6 | RL7 | RL8 | RL9 | RL10 | RL11 | RL12 | RL13 | RL14 |
Floor | 98 | 99 | 100 | 101 | 102 | 103 | 104 | 105 | 106 | 107 | 108 | 109 | 110 | 111 |
Connections
Connected to same network with IX devices:
Settings
Enable “lift control” and floor settings on monitor:
On monitor, tap “Settings” -> “Installer” -> “Parameter” -> “Others”
LIFT_CTRL_ENABLE: whether enable or disable lift control on this monitor.
DEVICE_FLOOR: Setup monitor’s floor and floor release time.
Public floor: Public floor, while tap RFID card on RLC card reader will release
Public time: Unlock via monitor, the public floor release time (NOT USE)
Public RLC time: Unlock via RLC card reader, the public floor release time.
Private floor: Private floor, while tap RFID card on RLC card reader or unlock via monitor will release
Private time: Unlock via monitor, the private floor release time
Private RLC time: Unlock via RLC card reader, the private floor release time.
Card data sync to IX-RLC:
On the IX850 with card data:
While in “Installer mode”, tap “Installer mode” -> “settings” -> “Access cards” -> “Card data” –> “Sync to device”, select the RLC and tap “Start sync”